KHS timer, figure 686 02 012

 

Product Features

  • for time-controlled water exchange of terminal or rarely flooded pipe sections
  • for controlled isolation of water installations and for time based water exchange to maintain an intended use
  • KHS timer with integrated timer switch
  • for connecting max. one KHS quarter-turn stop valve or KHS quarter-turn stop valve PLUS and a KHS overflow monitoring unit each
  • with detachable visual and / or acoustic error signal
  • with potential free contact for error transmission to BMS
  • with manual override button on control box
  • for wall installation
  • max. 16 programmable events
  • display with background light

Technical Data

  • min. ambient temperature 0 °C
  • max. ambient temperature 50 °C
  • protection class IP54
  • power supply 230 V AC
  • switching capacity 230 V, 2 A
  • floating alarm relay, max. 230 V, 2 A
  • own consumption 3 W

 

Produktfoto

 

Produktfoto

 

 

 

part no. D1
(mm)
H1
(mm)
H2
(mm)
L1
(mm)
L2
(mm)
T1
(mm)
T2
(mm)
kg
6860201200

4

58

44,5

160

148

79

50

0,472

 

 