KHS CoolFlow cold water cooler, figure 610 01

 

Product Features

  • as flow-through drinking water cooler for cooling drinking water with integrated circulation pump
  • for cooling and distributing the cold water as far as the tapping point outlet in the drinking water installation
  • adjustment range of PWC temperature 15 °C to 25 °C
  • consisting of PWM-controlled circulation pump with gunmetal housing and integrated check valve
  • consisting of PWM-controlled operating fluid pump
  • with diffusion-tight insulation fitted at the factory
  • pre-assembled
  • space requirements less than 1 m²
  • wetted metal parts made from dezincification-free and corrosion-resistant gunmetal, resistant to aggressive water, stainless steel and drinking water-approved plastics
  • easy operation with integrated commissioning wizard
  • low-noise operation
  • installation on the ground
  • incl. drinking water-side maintenance cut-offs
  • built-in operating fluid buffer tank
  • allows efficient operation of the cold water generator
  • connection to cold water generator hydraulically separated, integration of all cold water generators possible
  • recharging request through potential-free contact
  • compact design
  • plate heat exchanger made of stainless steel grade 1.4401/1.4404
  • electronic control unit for high control quality during operation
  • incl. Pt1000 measuring element
  • factory pre-assembled electrical connection of actuators and sensors to the control unit
  • maintenance and commissioning of the system on request

Standards and Approvals

  • plastic parts with KTW and W 270 approval
  • according to accepted materials list from German environmental agency
  • ÜA-Reg.-Nr. R-15.2.3-21-17048, WIEN-ZERT

Technical Data

  • pressure stage PN 10 drinking water side and PN 6 equipment side
  • min. ambient temperature 0 °C
  • max. ambient temperature 50 °C
  • max. cooling capacity 6.4 kW
  • power supply 230 V AC
  • electrical power input 185.5 W

 

Produktfoto

 

Produktfoto

 

 

 

part no. max. flow rate of
cold water
circulation pump (m³/h)
max. head of
cold water
circulation pump (m)
volume of
equipment
(l)
capacity
(KW)
A1A2A3A4D1
(mm)
D2
(mm)
D3
(mm)
H1
(mm)
H2
(mm)
H3
(mm)
H4
(mm)
L1
(mm)
L2
(mm)
T1
(mm)
T2
(mm)
T3
(mm)
kg
6100100000

2

11

100

6,4

G 1

G 1

Rp 1

Rp 1

640

590

13

805

660

392,5

840

161

210

400

381

345

72,000

 

CAD Modelle

part no. CAD Modell
6100100000

 

 

Downloads

 

 

Figur 61001

This website uses cookies

This website uses cookies to improve user experience. By using our website you consent to all cookies in accordance with our Cookie Policy.

Some cookies on this site are essential, and the site won't work as expected without them. These cookies are set when you submit a form, login or interact with the site by doing something that goes beyond clicking on simple links.

We also use some non-essential cookies to anonymously track visitors or enhance your experience of the site. If you're not happy with this, we won't set these cookies but some nice features of the site may be unavailable.