backflow preventer, type CA, figure 362 2G
Product Features
- to protect drinking water against backflow of fluids up to and including category 3 according DIN 1988-100
- wetted metal parts made from dezincification-free and corrosion-resistant gunmetal, resistant against aggressive water
- with stainless steel mesh at inlet
- maintenance-free backup cartridge
- with non-controllable pressure zone
- male union thread
- drain connection of plastic and gunmetal according to DIN EN 1717
- inlet and outlet with check cartridge
- free from dead spots
- for horizontal installation, drain valve down
- maintenance requirements in accordance with DIN EN 806-5 must be complied with
Standards and Approvals
- DVGW approval
- KIWA approval
- BELGAQUA approval
- plastic parts with KTW and W 270 approval
- according to accepted materials list from German environmental agency
- soundproofing certification according to DIN EN ISO 3822 Class 1
- DIN EN 14367 / EN 1717
- ÜA-Reg.-Nr. R-15.2.3-21-17048, WIEN-ZERT
Technical Data
- pressure rating PN 10
- max. operating temperature 60 °C
- short-term peak temperature 65 °C
part no. | DN | A1 | D1 (mm) | H1 (mm) | L1 (mm) | kg |
---|---|---|---|---|---|---|
3622G01500 | 15 | G 3/4 | 40 | 103 | 79,5 | 0,652 |
3622G02000 | 20 | G 1 | 40 | 103 | 79,5 | 0,657 |
Tender Text (pdod.de/en)
Downloads
- datasheet (PDF)
-
Spare Parts List
-
Kemper Product Guide for Building Technology
-
Flow Diagram
-
installation and operating instructions for backflow preventers, type CA
Figur 3622G