sampling valve for connection to angle stop valve, figure 188 00

 

Product Features

  • to sample drinking water and determine microbiological parameters according to the German TrinkwV drinking-water regulation
  • for simple retrofitting at the output of the angle valve
  • suitable for angle valves with 10 mm outlet compression connection
  • sampling pipe can be disinfected by flame
  • valve completely chrome-plated
  • PTFE seat gasket
  • inlet 10 x 1.25 pipe, outlet G3/8 male thread with compression nut for 10 mm pipe
  • valve is operated with 5 mm allen key (not in package)
  • made of brass, nickel plated
  • free from dead spots
  • incl. Allen key

Standards and Approvals

  • DVGW approval
  • plastic parts with KTW and W 270 approval
  • according to UBA valuation basis
  • DIN 50930-6

Technical Data

  • pressure rating PN 10
  • max. operating temperature 90 °C

 

Produktfoto

 

Produktfoto

 

 

 

part no. CADDNA1D1
(mm)
D2
(mm)
H1
(mm)
H2
(mm)
H3
(mm)
H4
(mm)
L1
(mm)
L2
(mm)
SW1
(mm)
SW2
(mm)
kg
1880001000

10

G 3/8

10

8

79

160

160

110

52,5

41

19

15

5

0,291

 

 

Downloads

 

 

Figur 18800