DUO stop valve water meter box, figure 870 07
Product Features
- internal parts made of gunmetal, stainless steel and plastic
- housing with G 2 coaxial thread for meter cartridges
- for wall surface installation, as a space-saving, galvanised steel case with versatile mounting options for existing wall systems
- with two permanently integrated, cast in a single piece, non-rotating and sound-insulated stop water meter combinations
- for installation of a cold and hot water
- with overflow cap and dirt protection during installation for the construction phase
- suitable for radio readouts
- can be covered by optional front panels
- with two flow rate-optimised direct seat valves and water meter housings
- maintenance-free EPDM spindle seal
- female pipe thread
- handle with blue or red dot for identification
- free from dead spots
- wear-resistant stainless steel valve seat
Standards and Approvals
- DVGW approval
- plastic parts with KTW and W 270 approval
- according to accepted materials list from German environmental agency
- DIN EN 1213
- ÜA-Reg.-Nr. R-15.2.3-21-17048, WIEN-ZERT
Technical Data
- inside micrometer 88 mm
- pressure rating PN 10
- max. operating temperature 70 °C
- short-term peak temperature 95 °C
part no. | DN | A1 | H1 (mm) | H2 (mm) | H3 (mm) | L1 (mm) | L2 (mm) | L3 (mm) | T1 (mm) | cv (m³/h) | kg |
---|---|---|---|---|---|---|---|---|---|---|---|
8700702000 | 20 | Rp 3/4 | 200 | 120 | 165 | 200 | 90 | 223,5 | 125 | 4,38 | 3,993 |
Tender Text (pdod.de/en)
Downloads
- datasheet (PDF)
-
Spare Parts List
-
Brochure Kemper Building Technology
-
installation and operating instructions for stop valve water meter boxes, DUO
-
Flow diagram
Figur 87007